14 .0 7. 20 23 1 3 64 2 5 a b c h f e d g i a b c i d j h e fg j k l m n k l Installation instructions – Flex branch 1.1 Essential tools: a) belt tightener’s, b) emery cloth, grain size 40, c) handsaw, d) drilling machine, e) plug bit, f) alcohol, g) lint-free cloth, h) blow torch with 50-60 mm head, i) hammer, j) leakage spray, k) gloves approved for epoxy work, l) plug welder, m) safety glasses, n) if required, belt sander. Essential materials: a) Flex branch, b) shrink cuff, c) mastic, d) fibreglass tape, e) 3x weld plugs, f) 3x vent plugs, g) heat- shrinkable shroud, h) long adhesive strip for heat-shrinkable shroud, i) short adhesive strip for branch, j) spacer. Additional: k) joint foam, l) branch piece Saw lengthwise through the flex branch as shown in the picture. The branch joint is pre-installed on the branch pipe before the branch piece is welded on. For installation of alarm wires, please see isoplus installation instructions for con- nection of alarm wires. The spacer is fitted at the top of the bend, ensuring that the joint will not be too close to the top of the bend. All 3 jacket pipe ends are cleaned carefully over the entire shrinking area, using a cloth moistened with alcohol. This set of assembly instructions applies to the Flex branch in the isoplus product catalogue section 16. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk 14 .0 7. 20 23 12 15 18 13 16 14 17 10 11 97 8 Tighten the branch on the sides of the main pipe using the main pipe as support. Fit the branch with an overlap. Installation instructions – Flex branch 1.2 In order to achieve increased flexibility, the corrugated part of the branch pipe is preheated to max. 60°C, using a soft gas flame. The flex branch is pulled over the main pipe. Remove the paper from the mastic. Wipe off the main pipe in longitudinal direction in the place where the adhesive strip is to be located, using a cloth moi- stened with alcohol. Sand carefully along the main pipe in the place where the adhesive strip is to be located. Wipe off a second time, along the main pipe and on the adhesive side of the adhesive strip. Mastic is applied on the main pipe only, as mastic is already integrated in the branch pipe. Affix mastic as shown in the picture. Fold the outer piece as shown to allow for when the paper is torn off later on. The centring of joint is marked. Mark the jacket pipe to allow the joint to have identical overlap on both sides of the joint. Sand all jacket pipe ends carefully with an emery cloth, over the entire shrinking/welding area. Use a belt sander for dimensions ≥ Ø 400. All 3 jacket pipe ends are cleaned again over the entire shrinking area, using a cloth moistened with alcohol. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk 2119 22 20 23 28 14 .0 7. 20 23 2127 24 25 26 29 30 Sand carefully the part of the branch jacket where the branch joint is to be shrunk. Installation instructions – Flex branch 1.3 Fibreglass tape is wound firmly around the main pipe as shown in the picture – with a cross in the centre and 4 turns in each spot. Remove the belt tighterners. Heat the adhesive side of the short adhesive strip thoroughly in its entire length. Carefully clean the branch jacket pipe over the entire shrin- king area, using a cloth moistened with alcohol. Mark the edge of the straight part of the branch pipe. Heat the flex part to max. 60° C. Use a blow torch with a min. head size of 50-60 mm. The flame should be yellow with blue tips. Pull the branch back with belt tighteners. Wipe off a second time – the part of the branch jacket whe- re the branch joint is to be shrunk, using a cloth moistened with alcohol. Preheat the jacket pipe to approx. 60°C with a soft gas flame. Remove the belt tighteners afterwards. Ensure that edge of branch pipe fits mark. Affix the adhesive strip. You must ensure that the adhesive on the strip melts and flows out along the sides of the strip. Place and heat the adhesive strip across the overlap of the flex branch. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk 3938 4240 41 31 3332 34 3635 37 14 .0 7. 20 23 Installation instructions – Flex branch 1.4 Drill foam holes at the top of the main pipe with a Ø 24.5 mm plug bit. Then position and heat the adhesive strip across the overlap on the flex branch. Once the shrinking is complete, check that there are no cold spots on the cuff and that the mastic is flowing out of both cuff ends. (see arrows) Correctly fitted vent plugFit the vent plugs – one on the main pipe and one on the branch pipe Drill the foam holes at the top of the branch pipe with a Ø 24.5 mm plug bit. Shrink the joint on the outermost 10 cm of the branch. Sand jacket pipe with the emery cloth around the entire sealing area. If double sealed: Let cool down to 50 – 60 °C. Apply alcohol to the cloth and carefully clean the casing pipe around the entire sealing area. Wipe off a second time in order to clean the part of the jacket pipe, which was ground, using a cloth moistened with alcohol. Remove the protective plastic from inside the shrink sleeve and position the joint with the centerline over the join. Preheat the entire sealing area. to min 60° C with a soft gas flame. Shrink the sleeve. Use a blow-torch with a min. head size of 50-60 mm. The flame should be yellow with blue tips. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk 48 49 43 44 45 46 47 50 51 52 14 .0 7. 20 23 The last vent plug is fitted after the foam is filled into the branch. Fill the correct foam quantity (see label on the branch) into the branch. IMPORTANT – foam must always be filled in through the lower foam hole in the main pipe. Installation instructions – Flex branch 1.5 Choose the joint foam number according to labelling on joint. Remove the plastic plug from the separating rail on the bag with joint foam. Remember protective gloves approved for epoxy work! Pull the rubber band away from the divider bar. PROTECTIVE GEAR: See separate instruction manual for foaming joints. IMPORTANT! When foaming joints, the temperature of the foam components must be between 20°C and 25°C. The proper temperature of the foam components during foaming is an extremely important prerequisite for the foam components to be able to be suciently mixed together, and is important for the chemical process. Foaming should only occur at pipe temperatures of min. 5°C and max. 50°C. Mixed foam must be poured into the joint max. 1 min. after you start mixing the components. Therefore, one person alone cannot mix more than 2 foam bags. Two persons must carry out the mixing process simultaneously for joints requiring more than 2 bags of foam. Remove the partition from the bag. IMPORTANT! Mix the foam components tho- roughly until the mixture has turned into a uniform light brown colour with no dark spots. . The mixing process must be intense, since the foam components will begin to react upon contact. The process is thus time-limited. The correct mixing process is crucial to the nal quality of the foam. Push the dark isocyanate down into the clear polyol. Shake the joint foam until the liquid has turned into a uniform light brown colour with no dark spots. Cut off the point of the bag. After completing the joint foaming process, the foam will be hardened after min. 20 minutes. Seal foamhole. Remove the vent plug. Remove all surplus foam with a knife. Chamfer the foam hole slightly before inserting the weld plugs. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk 5453 56 58 59 60 61 55 57 62 6463 14 .0 7. 20 23 Installation instructions – Flex branch 1.6 Wipe off the joint and jacket over the entire area where the shroud is to be located. Grind carefully the main pipe jacket next to the joint in the place where the shroud is to be located. Wipe off a second time the entire joint and the jacket next to the place where the shroud is to be located, using a cloth moistened with alcohol. Preheat the joint to approx. 60°C in the place where the shroud is to be located, using a soft gas flame. Weld beads must be visible from both the plug and the edge of the joint. Connect plug welder to 230 V-AC power source and set the temperature to 250°C. Mount the welding plugs in the foam holes. Insert the plug welder into the foam hole and hold it wit- hout pressing until an appropriate weld bead has formed both on the welding plug and on the edge of the foam hole. Insert the plug into the hole and hold it steadily until the weld has cured. Fit the heat-shrinkable shroud so that the cut corners are placed under the overlap. Remove the protective plastic from the shroud. Wipe a long adhesive strip with alcohol and heat the side with adhesive over its entire length. It is important that the cut ends of the heat-shrinkable shroud meet as shown in the picture, and the fiberglass tape is placed min. 30 mm inside the shroud. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk 67 6968 65 66 14 .0 7. 20 23 Installation instructions – Flex branch 1.7 After fitting the adhesive strip, the heat-shrinkable shroud is shrunk, using a soft gas flame from the centre and over the entire circumference of the pipe. Press the shroud firmly onto the joint around the branch pipe. Remove air pockets, if any. Once the shrinking is complete, check that there are no cold spots on the cuff and that the mastic is flowing out of both cuff ends. Heat the adhesive strip across the overlap of the heat- shrinkable shroud. Affix the adhesive strip. You must ensure that the adhesive on the adhesive strip melts and flows out along the sides of the strip. isoplus Piping Systems Ltd. · Plumtree Farm Industrial Estate · Plumtree Rd · Doncaster · DN11 8EW Tel. +44 1302 276976 · sales@isoplus.co.uk · www.isoplus.co.uk